430.22 Motor Branch Circuits.

The image above shows a portion of NEC Table 430.250 and a three-phase continuous duty motor nameplate.
Click to Enlarge
The image above shows a portion of NEC Table 430.250 and a three-phase continuous duty motor nameplate.

Once the full load current (FLC) rating of the motor has been determined, the branch circuit conductors can be sized. NEC® Section 430.22 requires conductors that supply a single motor used in a continuous duty application to have an ampacity of at least 125% of the motor FLC.

At 460 - 480 volts, the motor has a FLC of 27 amps. Since the motor is marked as a continuous duty motor, the FLC must be multiplied by 125% as follows:

27 X 125% = 33.75 amps. This is the minimum circuit ampacity to supply the motor.

Refer to NEC® conductor ampacity Table 310.16. If installing a type THWN copper conductor and terminating it at each end to 75°C terminals, a 10 AWG conductor rated at 35 amps would be sufficient as a branch circuit conductor.

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

430.22 Motor Branch Circuits.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What is the minimum circuit ampacity for a continuous duty motor that has been determined to have a FLC of 42 amps?

A: 23 amps.
B: 46 amps.
C: 42 amps.
D: 52.5 amps.
Please register or sign in for electrical continuing education courses.