Ampacity Table 310.16.

This is a portion of NEC Table 310.16. Not all values shown.
Click to Enlarge
This is a portion of NEC Table 310.16. Not all values shown.

When using conductor ampacity Table 310.16, it is important to understand why some conductor types are shown in both the 75°C column and the 90°C column. Types THHW and XHHW are listed in both temperature columns. A statement on the table, just above the temperature refers the reader to Table 310.4(A).

In Table 310.4(1), type THHW conductors are shown as 75°C rated conductors when used in wet locations and 90°C rated conductors when used in dry locations.

Similarly, type XHHW conductors are 75°C rated conductors when used in wet locations and 90°C rated conductors when used in dry and damp locations.

Selecting the correct temperature column from Table 310.16 for the above conductor types depends on the intended location of the conductor.

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Ampacity Table 310.16.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

According to NEC Table 310.16, a 2 AWG copper type XHHW conductor is shown in both the 75°C column and the 90°C column. If used in a damp location, what is the ampacity of the conductor?

A: 60 amps.
B: 95 amps.
C: 115 amps.
D: 130 amps.