Angle Pulls, U Pulls and Splices & Table 312.6(A).

Use the angle pull image to help answer the question.
Click to Enlarge
Use the angle pull image to help answer the question.

When installing insulated conductors of 4 AWG or larger, the minimum dimensions of pull or junction boxes installed in a raceway or cable run must comply with 314.28(A)(1) through (A)(3). The rules apply to “insulated” conductors for a reason. When installing large, insulated conductors, care must be taken to ensure that the conductor insulation is not compromised during the wire pull because the box is too small.

Section 314.28(A)(2) provides the minimum required dimension for an enclosure containing an angle pull, U pull or even splices. For angle pulls, U pulls or splices, the distance between each raceway entry inside the box or conduit body and the opposite wall of the box or conduit body shall not be less than six times the trade size of the largest raceway in a row but the exception below makes a special allowance for conductors that enter the back of an enclosure opposite a removable cover (see image).

“Exception: Where a raceway or cable entry is in the wall of a box or conduit body opposite a removable cover, the distance from that wall to the cover shall be permitted to comply with the distance required for one wire per terminal in Table 312.6(A)” as seen in part below:

Copper Conductor wire size Space Required
8–6 AWG 1 ½ inches
4–3 AWG 2 inches
2 AWG 2 ½ inches
1 AWG 3 inches
1/0–2/0 AWG 3 ½ inches
3/0–4/0 AWG 4 inches


NEC Table 312.6(A) provides minimum wire-bending space dimensions at terminals and minimum width of wiring gutters. Table 312.6(A) applies where conductors do NOT enter or leave the enclosure through the wall opposite their terminals which describes the typical installation where conductors enter the back of the enclosure opposite the removable cover.

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

 

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Angle Pulls, U Pulls and Splices & Table 312.6(A).

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image and the data above highlighted in yellow from NEC Table 312.6(A).

What is the minimum wire bending space required for dimension A if the SER cable contains 2/0 AWG copper conductors?

A: 4 inches.
B: 3 ½ inches.
C: 4 ½ inches.
D: 5 inches.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.