NFPA 70E 130.4(E)(b) Shock Protection Approach Boundaries.

Table 130.4(E)(b) in the NFPA 70E provides shock protection approach boundaries to exposed energized electrical conductors or circuit parts for DC systems.
Click to Enlarge
Table 130.4(E)(b) in the NFPA 70E provides shock protection approach boundaries to exposed energized electrical conductors or circuit parts for DC systems.

Table 130.4(E)(b) in the NFPA 70E provides shock protection approach boundaries to exposed energized electrical conductors or circuit parts for direct-current systems.

On the left side of the table is the nominal potential difference for the equipment being worked on. On the right side of the table is the restricted approach boundary. In the middle of the table is the limited approach boundary based on one of the two conditions:

  1. The presence of an exposed movable conductor
  2. The presence of an exposed, fixed in place circuit part

Example: A 500-volt DC circuit would have a nominal potential difference of 500 volts DC when measured positive to negative. This results in using the 301 V–1 kV row in the table.

In the example, the limited approach boundary for an exposed fixed circuit part is 3 foot, 6 inches. The restricted approach boundary is 1 foot.

Refer to the image of Table130.4(E)(b) to answer the question below.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

NFPA 70E 130.4(E)(b) Shock Protection Approach Boundaries.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image of Table130.4(E)(b) to answer the question below.

What is the limited approach boundary for an exposed fixed circuit part operating at 70kV?

A: 8 feet.
B: 10 feet.
C: 2 foot, 2 inches.
D: 2 foot, 9 inches.
Please register or sign in for electrical continuing education courses.