376.56(B) Power Distribution Blocks.

This power distribution block is not marked to indicate that it can be used on the line side of the service equipment.
Click to Enlarge
This power distribution block is not marked to indicate that it can be used on the line side of the service equipment.

Code Change Summary: Rules have been added pertaining to power distribution blocks installed in metal wireways.

Power distribution blocks are commonly used in gutter boxes or metal wireways for splicing conductors. Some gutter boxes where power distribution blocks are used are service gutters that contain service entrance conductors.

Through the inspection process it has been found that many power distribution blocks are installed on the line side of a service disconnect, inside a metal wireway, without first checking to see if the power distribution blocks are listed for such use.

UL product category QPQS states that “power distribution blocks marked "Suitable for Use on the Line Side of Service Equipment" (or equivalent) have been investigated for use on either the line side or the load side of service equipment”. That being said, if this marking is not present, then the power distribution blocks are not suitable to be used on the line side of the service disconnect.

In the 2014 NEC® this issue has been addressed in 376.56(B)(1).

As well, according to the new text added in 376.56(B)(2), its time to start keeping things organized in the wireway. The new language states that conductors must be arranged so the power distribution block terminals are unobstructed following installation.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code language:

376.56(B) Power Distribution Blocks.

(1) Installation. Power distribution blocks installed in metal wireways shall be listed.

2014 Code Language:

376.56(B) Power Distribution Blocks.

(1) Installation. Power distribution blocks installed in metal wireways shall be listed. Power distribution blocks installed on the line side of the service equipment shall be listed for the purpose.

(5) Conductors. Conductors shall be arranged so the power distribution block terminals are unobstructed following installation.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

376.56(B) Power Distribution Blocks.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for power distribution blocks installed in a wireway on the line side of the service equipment?

A: They must be marked with an AIC rating.
B: They must be listed for the purpose.
C: They must be covered with insulating tape after installation.
D: They must have a short circuit current rating of no more than 10,000 amps.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.