410.69 Identification of Control Conductor Insulation.

In the years to come, ballasts and drivers will have integral lead wires that do not use a grey wire for dimming or control features.
Click to Enlarge
In the years to come, ballasts and drivers will have integral lead wires that do not use a grey wire for dimming or control features.

Code Change Summary: New code section on the identification of lighting control conductors.

There are many controls, drivers, and lighting ballasts that have both a white conductor as a grounded neutral conductor, and a grey conductor for control or dimming. According to NEC® 200.7, white and grey conductors are reserved only for use as a grounded or neutral conductor.

It can be confusing when wiring luminaires equipped with both grey and white conductors since the electrical industry associates those colors only for a grounded or neutral conductor.

In the 2020 NEC®, a public input (code change proposal) was accepted to include a new code section to address the issue. The resulting language will require manufacturers to completely change their wiring device colors to ensure that any grey or white wires will only be for a grounded neutral conductor.

The new requirement will have a huge impact on product wiring diagrams, controls, drivers, and ballasts that have integral lead wires. Because of this, the new requirements in 410.69 have an effective date of January 1, 2022 to allow manufacturers time to catch up.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

This code section did not exist.

2020 Code Language:

N 410.69 Identification of Control Conductor Insulation. Where control conductors are spliced, terminated, or connected in the same luminaire or enclosure as the branch-circuit conductors, the field-connected control conductor shall not be of a color reserved for the grounded branch-circuit conductor or the equipment grounding conductor. This requirement shall become effective January 1, 2022.

Informational Note: See 200.6 for identification of grounded conductor and 250.119 for identification of equipment grounding conductor.

Exception: A field-connected gray-colored control conductor shall be permitted if the insulation is permanently re-identified by marking tape, painting, or other effective means at its termination and at each location where the conductor is visible and accessible. Identification shall encircle the insulation and shall be a color other than white, gray, or green.

Did You Like This? Let Us Know With A Like! Thanks!

410.69 Identification of Control Conductor Insulation.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What will be required in January of 2022 for the identification of control conductors spliced to branch circuit conductors in a luminaire?

A: The field-connected control conductor must be grey or green.
B: The field-connected control conductor shall not be grey unless reidentified in accordance with the exception to 410.69.
C: The field-connected control conductor shall be brown or yellow.
D: The field-connected control conductor shall be the same color as the hot branch-circuit conductor.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.