Fully Rated Systems.

In a fully rated system, all OCPD’s have an AIC rating equal to or more than the AFC at their line terminals.
Click to Enlarge
In a fully rated system, all OCPD’s have an AIC rating equal to or more than the AFC at their line terminals.

Overcurrent protective devices (OCPD’s) can be either Fully Rated or selected as a series combination rated system or Series Rated System.

In a Fully Rated system, all overcurrent devices are fully rated for the maximum amount of available fault current (AFC) at their line terminals which complies with the code language in NEC® 110.9. An example would be a 200-amp circuit breaker or fuse with an ampere interrupting capacity (AIC rating) of 42k AIC or 42,000 amps, installed in a panelboard where there is 38,000 amps of available fault current.

In the image, the example shows one electric panel with feed through lugs feeding another panel to the right. This example intends to show that after considering the type of feeder conductor running between the two panels, the length of conductor, the raceway type and the AFC at the beginning of the run of wire, there would be less AFC at the load end of the feeder but still a significant amount. The amount of AFC at each panel location would need to be calculated in order to comply with NEC® 110.9 and to be able to select the correct AIC rating of the circuit breakers since their purpose is to interrupt current at fault levels.

The image represents a Fully Rated System since all circuit breakers have an AIC rating equal to or greater than the AFC at their location.

Did You Like This? Let Us Know With A Like! Thanks!

Fully Rated Systems.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following represents a Fully Rated System?

A: An electric panel with circuit breakers having an AIC rating of 22kA where the available fault current is 19,000 amps.
B: An electric panel with circuit breakers having an AIC rating of 22kA where the available fault current is 24,000 amps.
C: An electric panel with circuit breakers having an AIC rating of 10kA where the available fault current is 24kA.
D: An electric panel with circuit breakers having an AIC rating of 10kA where the available fault current is 19,000 amps.